Lesson 7 of 8
Fuses and circuit breakers
I can explain fuses, circuit breakers and fuse ratings.Syllabus
Syllabus K223 / K224, 12(e). Explain fuses, circuit breakers and fuse ratings.
I can explain why switches, fuses and circuit breakers interrupt the live wire.Syllabus
Syllabus K223 / K224, 12(i). Explain why switches, fuses and circuit breakers interrupt the live wire.
Make a guess. You are not marked.
A circuit breaker trips when a faulty heater is switched on. Someone resets it at once without fixing the heater. What happens?
Show the answer
It trips again, because the fault still draws too large a current.
Resetting closes the switch, but the fault is still there. The large current flows again, so the breaker opens again. The fault must be fixed first.
In short
- A fuse is a thin wire that melts if the current gets too large. This breaks the circuit.
- Choose the smallest fuse rating above the appliance's normal current.
- A circuit breaker does the same job, but you can reset it.
- Both go in the live wire.
A fuse or circuit breaker cuts off the current when it gets too large. This stops cables from overheating and starting a fire.
Too much current can make a cable overheat. Protection must be in the live wire.
The fuse
A fuse contains a short, thin wire. If the current gets too large, the wire gets hot enough to melt. This breaks the circuit and stops the current. A melted fuse must be replaced, once the fault is fixed.
A fuse has a rating in amperes. This is the largest current it carries without melting. It does not melt the instant the current passes the rating; a larger current melts it faster.
Choosing the rating
Choose the smallest rating that is above the appliance's normal current. Then the fuse carries the normal current, but it melts soon in a fault.
Find the normal current first
A 460 W appliance at 230 V
The fuses on offer are 3 A and 13 A.
Normal current I = P/V = 460/230 = 2.0 A.
Choose 3 A, the smallest rating above 2.0 A. A 13 A fuse would let the current rise to more than six times its normal value before melting.
Fuses come in standard ratings. BS 1363 plugs, the type used in Singapore, take fuses made to the British standard BS 1362. Its preferred plug fuses are 3 A, coloured red, and 13 A, coloured brown.
Try it step by step
Work it out in steps: Normal current I = P / V in A, then Fuse rating to choose.
Show the answer
Problem 1.
Normal current I = P / V in A: I = P / V = 1150 / 230 = 5.0 A
Fuse rating to choose: A 5 A fuse is not above the 5.0 A normal current, so it leaves no margin, and 3 A is too small. So the 13 A fuse is fitted: the smallest rating above the normal current.
Problem 2.
Normal current I = P / V in A: I = 920 / 230 = 4.0 A
Fuse rating to choose: The 5 A fuse is the smallest rating above 4.0 A, so it carries the normal current and blows soonest in a fault.
Problem 3.
Normal current I = P / V in A: I = 460 / 230 = 2.0 A
Fuse rating to choose: The 3 A fuse is the smallest rating above 2.0 A.
The circuit breaker
A circuit breaker is a switch that opens by itself when the current is too large. Once the fault is fixed, you reset it with its switch; nothing needs replacing. In a home, each circuit has its own circuit breaker in the distribution board.
More detail (optional)
A residual current circuit breaker (RCCB) works differently. It compares the current in live with the current in neutral. If some current leaks away, for example through a person, it cuts the supply. A home RCCB in Singapore trips when about 30 mA leaks away.
Work from the appliance's own current. Do not use the socket's 13 A or the main circuit's rating. A fuse far above the normal current lets a fault go on for longer before it melts.
Check your understanding
A supplied model appliance takes 460 W at 230 V, with negligible starting surge and a suitable cord. Its permitted fuse options are 3 A and 13 A. Which choice follows from these conditions?
Show the answer
3 A: it carries the 2.0 A normal current and blows sooner if a fault occurs.
I = P/V = 460/230 = 2.0 A. Under the stated no-surge and suitable-cord conditions, 3 A is the lower permitted rating above the operating current. Real equipment needs its specified fuse.